ET602 Addressable thermovelocimetric detector

The thermovelocimetric addressable heat detector activates when the temperature exceeds a previously set level or when the rate at which this increase occurs is high, even if the set level has not been exceeded. The fixed threshold and thermovelocimetric temperature are individually selectable. Operates in “or” mode.

- +

Advantages

Universal base for all detector models. It features a bayonet coupling for easy and fast installation
Sleek and minimal design that adapts to any application, from residential to hospitality, without being invasive or impactful
Possibility to connect up to 32,000 devices on the loop
Diagnostic features for smoke detectors for predictive sensor degradation and thorough control of detector status:
-Dirty chamber
-Alarm indication
-Fault indication
Maintenance is facilitated as it is possible to directly view from the control panel which detectors need to be replaced
All devices on the loop are fully programmable from the control panel or via software
Possibility to name each detector for immediate identification, especially in the case of extensive systems
Available version with onboard isolator code ET612

Connections

2 loop poles

Standard

EN 54-5:2017+A1:2018

Power supply

24 Vdc from the loop

Average current draw

90μA

Led

2 RED ALARMS
360° visibility

Operation

Fixed threshold and thermovelocimetric NTC

Humidity

93% non condensing

Degree of protection

IP20

Temperature

-10°C / +70°C

Size

Dimensions (without base): mm 106Øx51h
Dimensions (with base): mm 106Øx59h

Or Register

ET602 Declaration Of Conformity 3.30 (ITA-ENG)

ET602 Technical Sheet A4.10 (ITA-ENG)

ET602 Technical Sheet 4.00 (ESP-ENG)

EN54 Certification 1922-CPR-0924