EF601 Addressable smoke detector

The smoke detector responds to the presence of visible smoke. The operating principle is based on the light scattering technique (Tyndall effect). Suitable for most applications, with a very rapid response even in the case of slow-burning or smoldering fires.

- +

Advantages

Universal base for all detector models. It features a bayonet fitting for quick and easy installation. Its sleek and minimal design adapts to various applications, from residential to hospitality, without being intrusive or overwhelming. It can connect up to 32,000 devices on a loop
Smoke detector diagnostics allow for predictive sensor degradation alerts and comprehensive monitoring of detector status, including dirty chamber indication, alarm signaling, and fault indication
Maintenance is simplified as the central unit can directly display which detectors need replacement
All devices on the loop are fully programmable from the central unit or via software. Each detector can be named for easy identification, particularly in extensive installations
A version with onboard isolator (code EF611) is also available

Connections

2 loops

Standard

EN 54-7:2018

Power supply

24 Vdc from loop

Average current draw

90μA

Led

2 RED ALARM
360° visibility

Passive isolator

No

Operation

TYNDALL EFFECT through photoemitter

Humidity

93% non condensing

Degree of protection

IP20

Temperature

-10°C / +70°C

Materials

White ABS plastic

Size

Dimensions (without base): mm 106Øx51h
Dimensions (with base): mm 106Øx59h

Or Register

EF601 Declaration Of Conformity 4.20 (ITA-ENG)

EF601 Technical Datasheet A5.10 (ITA-ENG)

EF601 Technical Datasheet 5.00 (ESP-ENG)

EN54 Certification 1922-CPR-0929