Advantages
Reset command relay.
Through this system, the module can reset smoke linear barriers without having to reactivate them directly from the control panel.
Management of a conventional zone by interfacing it with the addressable system.
Ideal for small existing conventional systems to avoid having to lay new wiring.
Size
95 x 53 x 24mm
Materials
Black ABS
Power supply
From loop 20-28Vdc
External power supply
20-30Vdc
Average consumption
90μA
Line fine resistance
3,9kΩ
Alarm resistance
1KΩ
Max output current
1A
Max cable length
100m max
Operating temperature
-10°C / +70°C
Relative humidity
93% non condensing
Degree of protection
IP20
Standard
EN54-18:2005,
EN54-18:2005/AC:2008