CF401R Conventional optical smoke detector with relay

Conventional smoke detector with onboard relay.
The operating principle is based on the Tyndall effect light dispersion technique.
Suitable for most applications, with a very rapid response even in cases of slow-burning or smoldering fires.
Used for connections to intrusion alarm panels or PLCs.

- +

Advantages

Universal base for all detector models. Equipped with bayonet fitting for easy and quick installation
Sleek and minimal design adaptable to various applications, from residential to hospitality, without being invasive or obtrusive
Equipped with onboard relay for stand-alone installations

Connections

Connection on line with EOL resistor of 3.9Kohm

Standard

EN 54-5:2017+A1:2018

Power supply

12-28Vdc

Led

2 RED ALARM LEDs with 360° visibility

Output

14mA at 24Vdc

Onboard relay

Yes
Relay Output: max 1A at 30Vdc
Type of Relay Output: NC (NO available on request)

Operation

TYNDALL EFFECT via photo emitter

Humidity

93% non condensing

Degree of protection

IP20

Temperature

-10°C / +70°C

Materials

White ABS plastic

Size

ф 106mm x 52mmH

Or Register

CF401R Declaration Of Conformity 3.20 (ITA-ENG)

CF401R Technical Datasheet A3.10 (ITA-ENG)

CF401R Technical Datasheet 3.00 (ESP-ENG)

CF401R UKCA Rev1.0

EN54 Certification 1922-CPR-0928