Size
406 x 306 x 200mm
Power supply
230Vac – 50/60 Hz ±10%
Secondary power supply
24VDC ±10%
Recommended battery
2x12V 2.3Ah AGM lead-acid
Maximum consumption (from mains)
5W
Maximum consumption (from battery)
4.5W
Alarm relay output portal Out 1 and Out 2
0.5A / 250VAC resistive
2A / 30VDC resistive
Alarm relay output portal
10A / 250VAC resistive
5A / 30VDC resistive
Maximum number of sensors
10 direct on the bus
160 through expanders
Node transmission
160ms
Sensor fault
Open circuit
Short circuit
Deterioration
Bus transmission protocol
Proprietary MODBUS RTU
Sensor tolerance
1% FS
Operating humidity
80% RH (non condensing)
Operating temperature
10° / +40°C
Startup time
90 seconds
Stabilization time
< 3 seconds
Distance from the "slave" unit
<1000 m
with connection on the same cable <100 m
Degree of protection
IP55