EX-CPxL Loop-addressed control panel – Excellent Series

Addressable analog fire control panel with dual 16-bit microprocessors.
An easy and intuitive user interface thanks to a 128×64 point display and the possibility of supervision via remote panel or PC software.

- +

Advantages

Network connection for up to 64 remote control panels
System supporting up to 256 loops for managing large and complex facilities
TCP/IP network connection for remote status monitoring via LAN
Mutual supervision of the control panel and auto-reset function
Bi-directional data communication between the control panel and connected devices on the loop
LED indicators to signal main events and conditions of the control panel
Built-in acoustic alarm in the control panel
LCD display for message visualization
Ability to connect conventional devices on the loop through dedicated addressed modules to interface between addressed and conventional devices

Outputs

1 supervised alarm output at 315mA
1 supervised fault output at 315mA
2 relay outputs with 3 contacts (C, NC, NO)
4 Open Collector outputs at 120mA
1 24Vdc output at 315mA

Programming

Zone programming in alarm, pre-alarm, test, out-of-service for maintenance modes
Output delay programming
Sensor programming through installation, acquisition, pre-set address, or via the EX-MPU loop programmer

Quantity of points

127 points per loop
63 independent geographical zones per loop

Standard

UNI EN 54-2:2007 (EN 54-2:1997 / AC:1999 / A1:2006);
EN 54-4:2007 (EN 54-4:1997 / AC: 1999 / A1:2002 / A2:2006)

Materials

Painted metal

Size

1 loop: 325 x 440 x 90mm
2 loop: 410 x 510 x 90mm
4 loop: 410 x 510 x 90mm

Connections

1 USB-B connection included
Provision for 1 opto-isolated RS485 serial for configuration and interfacing in local network
Provision for 1 LAN input for configuration and interfacing in local network
Provision for 1 opto-isolated RS232 or USB serial for smoke detector maintenance

Network

Up to 64 network addresses between control panels and repeater panels for managing over 30,000 addressed points in RS485.
Up to 16 network addresses between control panels and repeater panels in LAN

Software

Configuration and centralization software for setting up FDPNet network (license for graphical maps not included: see EX-SGR)
RS-485 network, Ethernet, or mixed network
Software for uploading and downloading points EX-UD
IP configuration software (EX-IP)

Event memory

Non-volatile memory up to 999 events with date, time, and event type

Display

Graphic display 128×64 alphanumeric points backlit

Additional features

2 batteries of 12V/7Ah (not included)

Or Register

EX-CP1L, EX-CP2L, EX-CP4L Technical Sheet 3.00

EX-CP1L, EX-CP2L, EX-CP4L Technical Sheet 3.00

EX-CPxL Manuale Installatore 4.20

EX-CPxL Installer Manual 4.20

EX-CPxL Manual Instalador 4.20

EX-CPxL Manuale Rapido 1.10

EX-CPxL Quick Installer Manual 1.10

EX-CPxL Manuel De Démarrage Rapide 1.10

EX-CP1L, EX-CP2L, EX-CP4L Certificate 1922-CPR-0917 (2019-2020) EN54-2, EN54-4

SKU: EX-CPxL Categories: ,